Search our site
 
 

 

   

PRODUCTS > UNITARY > PACKAGED UNITS

 

PACKAGED UNITS

Packaged Units (PQ Series)
Packaged Units (PL Series)
Packaged Units (HL Series)
 

Using proven reliable components, Cooline's Packaged Units are designed, assembled and produced to meet the highest quality standards. It will operate to the satisfaction of the End User years after years. That translates into peace of mind and sustained comfort.

Cooline air conditioning systems are manufactured under strict standards to meet the requirements of international quality assurance control.

Cooline™ Packaged Units (PQ Series)
  Range   3TR to 30TR (10kW to 105kW)

  Options &
  Accessories

 
 
  • UV Flow Light Emitters

  • Economizer
  • Electric Heater
  

  Key Features

 
  • Quality / Reliability

  • Simple selection / Design Integration

  • Simple Installation / Maintenance

  • Ease of operation

  Performance
  Data

 

Model No

Nominal Cooling Capacity

AIRFLOW

MBH

kW

CFM

M3/HR

PQ036 36 10.6 1200 2040
PQ048 48 14 1600 2720
PQ060 60 17.6 1800 3060
PQ075 72 21 2400 4080
PQ090 90 26.4 3000 5100
PQ100 102 30 3400 5780
PQ120 120 35 4000 6800
PQ150 144 42 4800 8160
PQ180 180 53 6000 10200
PQ210 210 62 7000 11900
PQ240 240 70.4 7500 12750
PQ300 300 88 9600 16320
PQ360 360 105 11250 19125

 

Notes:

  • Cooling capacities are rated in accordance with ARI standard 210. i.e. Ambient temperature 95° F (3° C).

  • Entering Air temperature 80° F DB / 67° F WB (26.7° C DB/19.4° C WB).

 


 

Cooline™ Packaged Units (PL Series)
  Range   3TR to 25TR (10kW to 85kW)

  Options &
  Accessories

 
 
  • Bottom & Side Air Discharge

  • Roof curb
  • Economizer up to 100% fresh air & enthalpy control
  

  Key Features

 

  Economical

  • High EER (Energy Efficiency Ratio)

  • High volumetric efficiency scroll compressors (6.2 tons & above)

  • Light weight, small footprint & versatile access panels

  • TEFC condenser fan motors

  Controls

  • Single point power supply (Number coded wires)

  • Large in-built NEMA style control panel

  • Microprocessor based controls

  • Intelligent air quality system

  Performance
  Data

 

Model No

Nominal Cooling Capacity

AIRFLOW

MBH

kW

CFM

M3/HR

PL036 36 10.6 1200 2040
PL048 48 14.1 1600 2720
PL060 60 16.4 2000 3400
PL075 75 22 2400 4080
PL090 90 26.4 3000 5100
PL100 100 29.3 3400 5780
PL120 120 35.2 4000 6800
PL150 150 43.9 4800 8160
PL185 180 52.7 5500 9350
PL225 218 63.9 6600 11220
PL240 258 75.6 7500 12750
PL300 324 94.9 9000 15300

 

Notes:

  • Cooling capacities are rated in accordance with ARI standard 210. i.e. Ambient temperature 95° F (3° C).

  • Entering Air temperature 80° F DB / 67° F WB (26.7° C DB/19.4° C WB).

 


 

Cooline™ Packaged Units (HL Series)
  Range   3TR to 23TR (10kW to 81kW)

  Options &
  Accessories

 
 
  • Low ambient kit for low temperature applications (For HL185-HL300)

  • Roof curb
  • Coated fins/copper fins for added corrosion resistance
  

  Key Features

 

  Economical

  • High EER (Energy Efficiency Ratio) during cooling mode

  • High COP (Coefficient of performance) during heating mode

  • High volumetric efficiency compressors

  Construction

  • Light weight, small footprint & versatile access panels

  • Flexible bottom/side discharge application

  • TEFC condenser fan motors

 

  Controls/Electrical

  • Single point power supply (colored & numbered coded wires)

  • Large in-built NEMA style control panel

  • Microprocessor based controls

  • Intelligent air quality system

  • Defrost control timer

  Performance
  Data

 

Model No

Nominal Cooling Capacity

Heat Pump Heating Capacity

AIRFLOW

MBH

kW

MBH

kW

CFM

M3/HR
HL036 35 10.25 34.2 10 1200 2040
HL048 49 14.4 48 14.1 1600 2720
HL060 58.5 17.14 60 17.6 2000 3400
HL075 70.2 20.6 74 21.7 2400 4080
HL090 85 24.9 87 25.5 3000 5100
HL120 120 35.2 123 36 4000 6800
HL150 140 41 133.5 39.1 4800 8160
HL185 170 49.8 162 51 5500 9350
HL225 207 60.6 195 57 6600 11220
HL240 223 65.3 214 62.6 7500 12750
HL300 280 81.9 265 77.6 9000 15300

 

Notes:

  • Cooling capacities are rated in accordance with ARI standard 210. i.e. Ambient temperature 95° F (3° C).

  • Entering Air temperature 80° F DB / 67° F WB (26.7° C DB/19.4° C WB).

  • Heating capacities are rated @ 47 F ambient,70 F dry bulb entering air & 60 F wet bulb entering air temperature.